HomeOmronCVE-2022-31204

CVE-2022-31204

HIGH
7.5CVSS
Published: 2022-07-26
Updated: 2024-11-21
AI Analysis

Description

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.

CVSS Metrics

Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Attack Vector
network
Complexity
low
Privileges
none
User Action
none
Scope
unchanged
Confidentiality
high
Integrity
none
Availability
none
Weaknesses
CWE-319

Metadata

Primary Vendor
OMRON
Published
7/26/2022
Last Modified
11/21/2024
Source
NIST NVD
Note: Verify all details with official vendor sources before applying patches.

Affected Products

omron : sysmac_cs1_firmwareomron : sysmac_cj2m_firmwareomron : sysmac_cj2h_firmwareomron : sysmac_cp1e_firmwareomron : sysmac_cp1h_firmwareomron : sysmac_cp1l_firmwareomron : cp1w-cif41_firmwareomron : cx-programmer